Download  Print this page

Rf Specifications; Central Station Messages; Alarm Condition; Trouble Reporting - Honeywell HWF2V-COM Installation And Setup Manual

Commercial fire communicator
Hide thumbs

Advertisement

RF Specifications

Frequency Bands
LTE
Band 2
HWF2V
HWF2A
Output Power
LTE
Class 3
WCDMA
Class 3
IMPORTANT NOTE ABOUT EXTERNAL ANTENNAS
Antenna may only be installed or replaced ONLY by a professional installer.
TO THE INSTALLER
HW2FA-COM: The external antenna gain shall not exceed 6.63 dBi for 700 MHz and 850MHz, 6.00 dBi for 1700 MHz, and
8.51 dBi for 1900 MHz. Under no conditions may an antenna gain be used that would exceed the ERP and EIRP power limits
as specified in FCC Parts 22H, 24E and 27.
HW2FV-COM: The external antenna gain shall not exceed 6.94 dBi for 700 MHz 6.00 dBi for 1700 MHz, and 9.01 dBi for
1900 MHz. Under no conditions may an antenna gain be used that would exceed the ERP and EIRP power limits as specified
in FCC Parts 22H, 24E and 27.

Central Station Messages

Alarm Condition

Power On / Reset
ECP Supervision (Compromise Indication)
Primary Communication Path Supervision
Secondary Communication Path Supervision
Periodic Cell Comm Path Test Failure
(We do not send a restoral R358 C0803, we send a failure message every day
after the radio attempts to test and fails.)
Application Code Update
Application Code Update Failure
Module Firmware Update
Module Firmware Update Failure

Trouble Reporting:

The HWF2-COM does not support low/missing battery or AC loss reporting.
Power (low/missing battery or AC loss) is monitored by the PB1 module, which
triggers the trouble buzzer and turns on the appropriate LED. NOTE: Trouble
buzzer sounds during AC Loss only (A Low/missing battery does not trigger
the buzzer).
HWF2-COM communicator fault
The Fire Panel sends out a E380, and E352 message via Telco #1, these are
then relayed to the central station via the HWF2-COM.
Telco line 1 fault
The Fire Panel sends out a E380, and E351 message via Telco #2, these are
then relayed to the central station via the HWF2-COM.
Telco line 2 fault
Fire Panel sends out a E380, and E352 via Telco #1, these are then relayed to
the central station via the HWF2-COM.
Test

AlarmNet Messages

Communication failure. (Possible Compromise Indication)
Authorized Radio Substitution
Unauthorized Radio Substitution Attempt
Service Termination
LTE
Band 4
X
X
X
X
23dBm
24dBm
LTE
LTE
Band 5
Band 12
X
X
20
LTE
WCDMA
Band 13
Band II
X
X
X
Alarm Code
E339 C0803
E355 C0000
E350 C0951
E350 C0952
E358 C0803
E903 C08xx
E904 C08xx
E365 C08xx
E366 C08xx
E380, E351,
E352 codes as
appropriate.
5555 5555 9
E359 0 C950
00D0 010C 0
00D0 010E 0
00D0 020E 0
WCDMA
Band V
X
Restore Code
N/A
R355 C0000
R350 C0951
R350 C0952
N/A
R903 C08xx
(success)
R365 C08xx
(success)
N/A
N/A
R359 0 C950
N/A
N/A
N/A

Advertisement

Table of Contents
loading

  Related Manuals for Honeywell HWF2V-COM

This manual is also suitable for:

Hwf2a-com