Tightening Torques - PIETRO FIORENTINI GOVERNOR 30051 Use And Maintenance Manual

Low pressure gas regulators
Hide thumbs Also See for GOVERNOR 30051:
Table of Contents

Advertisement

Step
Action
Checking the slam-shut device for tripping due to
maximum/minimum downstream pressure:
1. open the external pressure source by increasing the
pressure by approx. 2 mbar/s until the maximum
pressure lockout is triggered when the reset exten-
sion is triggered;
2. check that the tripping value of the slam-shut device
is ± 15% with respect to the value indicated on the
4c
nameplate applied (pdso);
3. reset the regulator lock;
4. close the external pressure source;
5. close the tap located upstream of the regulator;
6. open the tap of the external pressure source so that
the pressure decreases by approx 2 mbar/s.
7. check that the tripping value of the slam-shut device
is ± 15% with respect to the value indicated on the
nameplate applied (pdsu).
5
Disconnect the external pressure source outlet.
6
Close the downstream pressure outlet (Step 3).
7
Open the shut-off valve which was closed in Step 1.
8
Carry out commissioning as described in Section 7.4.
9
Check that there are no leaks at the shut-off pressure outlet in Step 6.
9.3 -

TIGHTENING TORQUES

NOTICE!
For the tightening torques of the swivel joints, refer to standards: NF E29-533: 2014 and NF E29-536: 2017.
71
LOW-PRESSURE GAS REGULATOR
|
MAINTENANCE AND FUNCTIONAL CHECKS
Use, maintenance and warning instructions
Tab. 9.50.
|
REV. A
EN

Hide quick links: