4 - DESCRIPTION AND OPERATION

4.1 -

VERSIONS, MODELS AND CONFIGURATIONS

NOTICE!
The different versions of the equipment must be:
contractually established;
set up at PIETRO FIORENTINI S.p.A. plants only
Typical versions of GOVERNORS are listed in Tab. 4.13:
Type
Image
Standard
Version
Zero Version
Ratio Ver-
sion
Goval Ver-
sion
Painted
version
25
Description
This version has a maximum inlet pressure of 0.5 bar and can be supplied with:
internal filter element to protect the plugs;
slam-shut valve for maximum and minimum downstream pressure.
This version can be used as a zero device, i.e. keeping the downstream pres-
sure at zero when the flow demand changes.
This version can be used as a gas/air ratio device keeping the gas/air mixture
constant as the flow rate changes.
NOTICE!
The device can be calibrated to achieve a 1:1 gas/air mixture.
Compared to the standard version, this version has a max. inlet pressure ex-
tended to 1 bar.
This version is suitable for:
-
marine environments (against salt corrosion);
highly humid atmospheres.
LOW-PRESSURE GAS REGULATOR
|
DESCRIPTION AND OPERATION
Use, maintenance and warning instructions
Tab. 4.12.
|
REV. A
EN