Putting The Ratio Version Regulator Into Service - PIETRO FIORENTINI GOVERNOR 30051 Use And Maintenance Manual

Low pressure gas regulators
Hide thumbs Also See for GOVERNOR 30051:
Table of Contents

Advertisement

8.4.3 - PUTTING THE RATIO VERSION REGULATOR INTO SERVICE

To commission the Ratio version regulator (B), proceed as shown in Tab. 8.48.:
Step
Action
1
Partially open the downstream air vent valve when present.
2
Slowly open upstream shut-off devices (e.g. solenoid valves, OPSO slam-shut valve, etc.).
Wait for the downstream pressure to stabilise at the spring setting P2 indicated on the nameplate.
3
NOTICE!
For the values on the rating plate, please refer to section 2.8 'Applied rating plates' et seq.
Proceed as described in section 7.5.3 'Ratio Version Adjustments'.
NOTICE!
4
Turn the adjusting screw to calibrate the regulator by checking the gas outlet pressure with a
pressure gauge.
5
Close the air vent valve.
GAS
AIR
67
A
Fig. 8.21.
C
B
D
Commissioning (Ratio version)
LOW-PRESSURE GAS REGULATOR
Tab. 8.47.
|
COMMISSIONING
Use, maintenance and warning manual
|
REV. A
EN

Hide quick links:

Advertisement