Chapter 5 Installation
Description / Panels
The HotSwap MBP has a manual Bypass rotary switch with two positions:
- the load is supplied by the UPS
- the load is supplied directly by the AC power source
Two lights indicate the HotSwap MBP power status:
can be safely turned to UPS position
mode" (Bypass switch turned to Bypass position)
Allows to safely switch off the AC source of the UPS, for UPS maintenance / replacing
A signal cable, with RJ11 connector to plug to the UPS, allows the communication to the UPS
to manage the MBP status, and the indication on UPS display panel of both following status:
MBP connection to UPS
Bypass switch position
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
green light: when active, the UPS output is available, the Bypass switch
red light: when active, indicates that the HotSwap MBP is on "Bypass
Input/Output terminal blocks
Input/Output cables for connection to the UPS
Bypass terminal blocks for connection to the
UPS
Normal AC source switch
Bypass AC source switch
Signal cable for MBP detection to the UPS
Manual Bypass switch
4x 16 A outlets
UPS supply green light
mode red light