Appendix A. Specifications
11 kVA UPS units
The below table is for the
Lenovo and IBM RT11kVA 6U Rack or Tower UPS (200-240VAC), 5594-9KX
•
Lenovo and IBM RT11kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC), 5594-8PX
•
UPS units.
Load
Percent
Watt
25 %
2500 W
50 %
5000 W
75 %
7500 W
100 %
10000 W
Note: The backup / run times in the above table has been measured with fresh, new batteries. The
battery backup / run times are approximate and will vary with equipment, configuration, battery
age, and temperature.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
Backup / Run Time in minutes
Base UPS
1x EBM
25
10
5.5
3
2x EBMs
60
97
25
42
15
25
10
18
3x EBMs
4x EBMs
136
163
61
37
25
79
48
34
277