Appendix A. Specifications
Weights and dimensions, Power Module
Machine Type - Model D x W x H ( mm / inch )
5594-8PX, 8 kVA
5594-8KX, 8 kVA
5594-9PX, 11 kVA
5594-9KX, 11 kVA
Minimum rack depth for UPS with Maintenance Bypass Panel: 900 mm (35.4 inches)
Weights and dimensions, Extended Battery Module including batteries
Machine Type – Model D x W x H ( mm / inch )
5594-9BX
Environmental and safety standards

EMC certifications

EMC (Emissions) -
for output cable < 10 m
EMC (Immunity)
Agency markings
Operating temperature
Storage temperature
Transit temperature
Relative humidity
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
700 x 440 x 130 (27.6 x 17.3 x 5.1)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
680 x 440 x 130 (26.8 x 17.3 x 5.1)
IEC/EN 62040-1: 2008
IEC/EN 62040-2: 2006 Cat. C2
IEC/EN 62040-3: 2011
CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
CE / C-Tick
0 to 40 °C (32 to 104 °F) in Online mode, with linear derating for
altitude
0 to 40°C (32 to 104°F) with batteries
-15 to 60 °C (5 to 140 °F) without batteries
-25 to 55 °C (-13 to 130 °F)
0 to 95 % no condensing
Weight ( kg / lbs )
23 / 51
19 / 42
23 / 51
21 / 46
Weight ( kg / lbs )
65 / 143
263

Advertisement