Chapter 2 UPS Safety Instructions
The MBP connection instructions and operation described in the manual must be
followed in the indicated order.
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with
branch circuit overcurrent protection for :
- 50A rating, for 8kVA models,
- 70A rating, for 11kVA models,
in accordance with the National Electric Code.
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible. The
unit can be disconnected from AC power source by opening this circuit breaker. This
circuit breaker is used for backfeed protection and must comply with IEC/EN 62040-1
(the creepage and clearance distances shall meet the basic insulation requirements for
pollution degree 2).
The unit can be disconnected from AC power source by opening this circuit breaker, and
if still connected to UPS, by previously shutting down the UPS
Disconnection and overcurrent protection devices shall be provided by others for
permanently connected AC input (Normal AC/Bypass AC) and AC output circuits.
Check that the indications on the rating plate correspond to your AC powered system
and to the actual electrical consumption of all the equipment to be connected to the
system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment
and shall be easily accessible
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -15 ºC / 5 ºF to +50 ºC / 122 ºF.
The system is not for use in a computer room AS DEFINED IN the standard for the
Protection of Information Technology Equipment.

Special precautions

The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling
operations.
All handling operations will require at least two people (unpacking, lifting, installation in
rack system).
Straps are provided only for unpacking manually the unit from the carton; don't use the
straps to carry the unit around. The unit can slip from the straps during handling (risk of
injury and product damage):
- keep 12 in / 30 cm minimum distance between the straps
- lift the unit carefully and keep it at low height
- keep the unit horizontal during unpacking.
6
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG