Chapter 6 Power cables connection
Single phase MBP power cables connection
Attention!
This type of connection must be carried out by qualified electrical personnel
•
Before carrying out any connection, check that the upstream protection device (Normal
•
AC source) is open " " (Off)
Before proceeding to connect the HotSwap MBP to the UPS, make sure the UPS has
•
been properly shut down. See also
10 UPS maintenance
Always connect the ground wire first
•
Pay attention to the pin assignment on the terminal blocks!
UPS Power Module terminal block
L1
N / L2
PE / GND
1. Remove the top cover
2. Punch the knockouts of the MBP I/O UPS connection cover
fittings inside.
86
for details.
of the MBP I/O "UPS connection" cover
Shutting down the UPS completely
Maintenance Bypass Panel terminal block
PE / GND
N / L2
L1
and insert 2 provided conduit
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
in
after removing the 3 screws.
Chapter