Chapter 6 Power cables connection
Single phase MBP power cables connection
Attention!
This type of connection must be carried out by qualified electrical personnel
Before carrying out any connection, check that the upstream protection device (Normal
AC source) is open " " (Off)
Before proceeding to connect the HotSwap MBP to the UPS, make sure the UPS has
been properly shut down. See also
10 UPS maintenance
Always connect the ground wire first
Pay attention to the pin assignment on the terminal blocks!
UPS Power Module terminal block
L1
N / L2
PE / GND
1. Remove the top cover
2. Punch the knockouts of the MBP I/O UPS connection cover
fittings inside.
86
for details.
of the MBP I/O "UPS connection" cover
Shutting down the UPS completely
Maintenance Bypass Panel terminal block
PE / GND
N / L2
L1
and insert 2 provided conduit
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
in
after removing the 3 screws.