Chapter 10 UPS maintenance
Step 9.
Verify that the
power is available to the MBP. Do not continue to the next step if the
light on the MBP is off. If the green light is off and the manual rotary switch is moved to the
UPS position, the load will lose power.
Step 10. Single Phase UPS unit only, 5594-8KX and 5594-9KX
Push the yellow tab on the MBP rotary switch back in.
All UPS units
Move the rotary switch to the the UPS position.
The
by the UPS.
Step 11. On the UPS, select
Step 12. Check that the UPS is in Online mode by checking its display panel. The load is now
protected by the UPS.

Recycling the used equipment

Contact your local recycling or hazardous waste centre for information on proper disposal of
the used equipment.
DO NOT dispose of batteries in a fire or expose them to temperatures higher than
Attention!
100 °C (212 °F). Battery packs might explode.
DO NOT open or mutilate the batteries. Released electrolyte is harmful to the skin and
eyes. It can be toxic.
Dispose of the battery as required by local ordinances or regulations.
DO NOT discard waste electrical or electronic equipment (WEEE) in the trash. For
proper disposal, contact your local recycling/reuse or hazardous waste centre.
DO NOT discard the UPS or the UPS batteries in the trash. This product contains
sealed lead acid batteries and must be disposed of properly. For more information,
contact your local recycling/reuse or hazardous waste centre.
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
green light on the MBP is on, indicating that the UPS output
red light on the MBP turns off, indicating that the load is now powered
Control
Go back normal
to put the UPS into Online mode.
green
137