Appendix A. Specifications
Hotswap MBP specifications (continued)
Overall dimensions D x W x H
(mm / in)
Weight (kg / lb)
Nominal voltage
Frequency
Input nominal current
Maximal power
Safety Standards
EMC
Performance
ESD
Radiated field
EFT
Fast transients
Electromagnetic field
Conducted magnetic field
Marking
Operating temperature
Storage temperature
Transit temperature
Humidity
Operation Altitude
Transit Altitude
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
8 / 11 kVA, Single phase
172 x 336 x 130 mm / 6.8 x 13.2 x 5.1 in
Minimum rack depth for UPS with MBP: 900 mm (35.4 inches)
6.2 / 13.7
200 - 240 V ~
50/60 Hz
50 A
11000 VA
IEC/EN 62040-1 / Ed.1: 2008.
UL 1778 4th edition
IEC 62040-2 / Ed.2: 2005. EN
62040-2 / Ed.2: 2006. FCC part
15 Class A
IEC/EN 62040-3 / Ed.2.0: 2011
IEC 61000-4-2 : level 3
IEC 61000-4-3 : level 3
IEC 61000-4-4 : level 4
IEC 61000-4-5 : level 4
IEC 61000-4-6 : level 3
IEC 61000-4-8 : level 4
cULus Listed / CE
0 to 40 °C (32 to 104 °F)
-15 to 60 °C (5 to 140 °F)
-25 to 55 °C (-13 to 130 °F)
0 to 95 % non-condensing
Up to 3,000 m (9,843 ft) above sea level with 10 % derating per
1000 m
Up to 10,000 m (32,808 ft) above sea level
8 / 11 kVA, Three phase
5.5 / 12.1
350 - 430 V ~
IEC/EN 62040-1 / Ed.1: 2008
IEC 62040-2 / Ed.2: 2005 EN
62040-2 / Ed.2: 2006
CE
265