Chapter 6 Power cables connection
3. Insert the provided conduit with blue colour coding
SOURCE" conduit fitting take care to leave the conduit end with blue label on opposite side (for
connection to UPS).
4. Connect the 3 wires of this blue colour conduit
terminal blocks.
5. Insert the provided conduit with red colour coding
fitting take care to leave the conduit end with red label on opposite side (for connection to UPS).
6. Connect the 3 wires of this red colour conduit
blocks.
7. Put back the MBP I/O "UPS connection" cover
8. Put back the top cover
9. Remove the I/O terminal blocks cover of the UPS
10. Punch the Input and Output knockouts of the UPS I/O TB cover and insert 2 provided conduit
fittings inside.
11. Insert the conduits
cover, following colour coding on the conduits and the UPS I/O TB cover (blue for UPS Input / red
for UPS Output) – also do not remove the UPS Input Bypass jumper inside the UPS I/O TB cover
12. Connect the wires of the conduit with blue colour coding 3 to the "NORMAL AC SOURCE"
terminal blocks of UPS, and the wires of the conduit with red colour coding 4 to the "OUTPUT"
terminal blocks of UPS, see
UPS Power Module
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
of the MBP I/O "UPS connection" cover
and
through the previously mounted conduit fittings of the UPS I/O TB
Figure 31 Principal connections - Maintenance Bypass Panel,
for more details
, through the "TO UPS NORMAL AC
to the "TO UPS NORMAL AC SOURCE" MBP
, through the "FROM UPS OUTPUT" conduit
to the "FROM UPS OUTPUT" MBP terminal
and secure it with 4 screws on the MBP casing.
and secure it with 3 screws.
87