Appendix A. Specifications
11 kVA UPS units
Overview - 11 kVA UPS units
Specification
General
Part Number
Country
Form factor
Topology
EBM Support
EPOW connector
MBP Required
Network Management Card
VA/Watts rating
Efficiency (on utility power)
Transfer time
Leakage current
Energy Star compliant
6U Rack or Tower UPS RT8kVA and RT11kVA IUOMG
RT11kVA 6U Rack or Tower
UPS (200-240VAC)
5594-9KX
5594-RU8, FC A544
World Wide
6 U Rack or Tower
Online, double conversion, sine wave output
HE (High Efficiency) mode: Line interactive
Yes (55949BX)
Yes
Yes, single phase
Yes, shipped with UPS in the
box, needs to be installed
11000 VA
10000 W
Online mode: Up to 94.5%
High efficiency mode: Up to 98%
Online mode: 0 ms (no break)
High efficiency mode: 10 ms maximum (due to loss of utility
power)
Leakage current of the equipment is up to 5% of input current for
the leakage current defined by the Input ground to UPS chassis
per the UL standard 60950 5.1 Touch current and protective
conductor current.
For additional information see the section
in
Chapter
12.
Yes
RT11kVA 6U 3:1 Phase Rack
or Tower UPS (380-415VAC)
5594-9PX
5594-RU8, FC A547
Yes (55949BX)
Yes
Yes, three phase
Yes, shipped with UPS in the
box, needs to be installed
11000 VA
10000 W
Leak current information
No
255