Operation
Index
Name
80x0:04
Diag TestPulse active
80x0:05
Module Fault Link active
80x1:01
InputFilterTime
80x1:02
DiagTestPulseFilterTime
5.3.7
Process image of the EL1918
The process image of the EL1918 consists of 7 bytes process data in the input and 6 bytes process data in
the output.
Fig. 25: Process image of the EL1918
The assignment of the individual signals in the safe data is listed in the following table.
Name
FSIN Module1.Input
FSIN Module1.Module Fault
FSIN Module2.Input
FSIN Module2.Module Fault
FSIN Module3.Input
FSIN Module3.Module Fault
44
Default value/
unit
TRUE / Boolean Activation of test pulses for the
TRUE / Boolean If a module error occurs in this module, a
0x000A / 0.1 ms Input filter of the safe input. Following this
0x0002 / 0.1 ms Input filter for the test pulse signal
Process
Bit position Description
image
IN
0.0
IN
0.1
IN
0.2
IN
0.3
IN
0.4
IN
0.5
Version: 2.0.0
Description
corresponding input module
module error is also set for all other
modules of this TwinSAFE component for
which this parameter is also set to TRUE.
time the internal input signal changes to
the applied signal state.
Safe input 1
Module error information for input 1
Safe input 2
Module error information for input 2
Safe input 3
Module error information for input 3
EL1918 and EL1918-2200