Fig. 23 Connection Tab Of The Alias Device; Fig. 24 El1918 Parameters - Beckhoff EL1918 Operation Manual

Twinsafe terminal with 8 digital fail-safe inputs
Hide thumbs Also See for EL1918:
Table of Contents

Advertisement

Under the Connection tab you can make further settings, e.g. the mapping of the info data or the behavior in
case of a module error.
Fig. 23: Connection tab of the alias device
The Safety Parameters tab contains the parameters of the EL1918 to be set. The parameters are set
separately for each input. Objects 0x8000 and 0x8001 are available for input 1. For all other inputs, the CoE
index is increased by 10 hex each, so that objects 0x8070 and 0x8071 are available for input 8.
Fig. 24: EL1918 parameters
Index
Name
80x0:01
ModuloDiagTestPulse
80x0:02
MultiplierDiagTestPulse
EL1918 and EL1918-2200
Default value/
Description
unit
0x00 / integer
Modulo value for the frequency of
generating a test pulse.
0 -> every time
1 -> every second time
...
0x01 / integer
Length of the test pulse in multiples of
400 µs
Version: 2.0.0
Operation
43