Huawei UPSJZ-T Series User Manual page 35

Table of Contents

Advertisement

UPSJZ-T-(1 kVA–3 kVA)
User Manual
No.
4
5
6
7
2022-08-15
Item
Cable labels
Ground cable connection
Spacing between cable ties
Operating environment
Expected Result
Both ends of each cable are labeled.
Labels are easy to understand.
The UPS ground cable is securely
connected to the equipment room
ground bar. Use a multimeter to
measure the resistance between the
UPS ground cable and the equipment
room ground bar. The resistance is less
than 0.1 ohm.
Distances between cable ties are the
same, and no burr exists.
The inside and outside of the cabinet
are free from conductive dust or other
sundries.
3 Installation
30