UPSJZ-T-(1 kVA–3 kVA)
User Manual
Battery Routine Maintenance
Table 7-2 Battery routine maintenance
Item
Battery
management
alarm
Battery
appearance
Battery operating
temperature
2022-08-15
Expected Result
No battery
management
alarm is
generated.
1. The surface is
clean and free
of stains.
2. The battery
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from acid
leakage.
5. Batteries are
not deformed
or bulged.
1. The battery
ambient
temperature is
25±5°C.
2. The battery
operating
temperature
must be lower
than the
ambient
temperature
plus 20°C.
3. Battery charge
and discharge
conditions
meet the
requirements
specified in the
battery
specifications.
7 Routine Maintenance
Troubleshooting
Identify the alarm
cause based on
the alarm
information.
If the battery
appearance is
abnormal, contact
technical support.
1. Identify the
cause of the
abnormal
battery
operating
temperature.
2. If the fault
persists,
contact
technical
support.
Maintenance
Interval
Monthly
Monthly
Monthly
86