Huawei UPSJZ-T Series User Manual page 102

Table of Contents

Advertisement

UPSJZ-T-(1 kVA–3 kVA)
User Manual
Specifications
Battery type
Battery capacity
Backup time
Rated
charging
current of the
charger
Float charge
voltage
Equalized
charge
voltage
Table 9-7 Battery box backup specifications for tower-mounted UPSs with long
backup time
Battery
Box
One battery
box
Two battery
boxes
2022-08-15
1 kVA
Valve-regulated lead-acid (VRLA) battery, 12 V
DC
9 Ah
Standard
> 4 minutes (at full rated load)
backup time
model
Long backup
Depends on the capacity of the external
time model
batteries.
Standard
1 A
backup time
model
Long backup
4 A
time model
Standard
27.3 V DC
backup time
±1%
model
Long backup
41.0 V DC
time model
±1%
Standard
28.3 V DC
backup time
±1%
model
Long backup
42.5 V DC
time model
±1%
Load
1 kVA UPS
Backup Time
(Minute)
100%
15
75%
21
50%
39
25%
77
100%
36
75%
47
50%
83.0
9 Technical Specifications
2 kVA
54.7 V DC
±1%
82.1 V DC
±1%
56.6 V DC
±1%
84.9 V DC
±1%
2 kVA UPS
3 kVA UPS
Backup Time
Backup Time
(Minute)
(Minute)
17
17
25
25
45
45
85
85
39
39
55
55
95
95
3 kVA
82.1 V DC
±1%
109.4 V DC
±1%
84.9 V DC
±1%
113.3 V DC
±1%
97

Advertisement

Table of Contents
loading

Table of Contents