Huawei UPSJZ-T Series User Manual page 72

Table of Contents

Advertisement

UPSJZ-T-(1 kVA–3 kVA)
User Manual
Alarm ID
Cause ID
42
42
66
1
2022-08-15
Name
Severity
Internal
Critical
fault
Output
Minor
overload
Clearance
Trigger
Mode
Condition
This
The
alarm
voltage of
needs to
each
be
battery
manually
decreases
cleared.
to below
10 V
when the
charger
has no
output
and the
UPS
inverter is
started.
The alarm
The
is
inverter
automatic
output
ally
load is
cleared.
more
than
105% of
the rated
load.
4 Control Panel
Impact
Solution
on the
System
The UPS
Possible
transfers
cause:
to bypass
The
mode.
charger
switch is
faulty.
Measure:
Contact
your
dealer or
technical
support.
This
Possible
alarm
cause:
does not
The load
affect the
exceeds
power
the rated
supply.
inverter
loading
capacity.
Measure:
Lower the
load or
replace
the UPS
with a
larger-
capacity
UPS.
67