Huawei FusionCol8000-E260 Quick Manual page 63

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E260:
Table of Contents

Advertisement

FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (Building Scenario)
Categor
y
Compres
sor
Differen
tial
pressure
switch
Air filter
Table 10-2 Cable connection checklist
Check Item
Cables are intact and free from sharp bends.
No open or short circuit, or incorrect connection occurs in
electrical circuits.
All cables for the unit are properly connected as required.
The rated specifications of the upstream general switch
meet the maximum current requirement.
All cables, terminals, and screws are secured.
The device is properly grounded.
Issue 03 (2022-11-25)
Check Item
The water tank filter is secured.
The liquid level sensor is not stuck.
Pipes are connected securely without leakage.
The water tank is free of foreign matter, and
the water tank filter and drainage port are not
blocked.
The drip pan is free of sundries inside and its
drainage port is unblocked.
The sheet metal fasteners on the compressor
have been removed.
The bolts for securing the compressor are
tightened.
The pressure inlet tube is secured using cable
ties and not deformed.
The pressure inlet tube is not blocked or bent.
The protective film on the air filter has been
removed.
The air filter is correctly installed according to
the airflow direction labeled on the frame.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Verifying the Installation
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
56