FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (Building Scenario)
Figure 4-2 Installing a water pipe
Step 4 Install the spray drainpipe.
1.
2.
----End
Pipe Anti-freezing
When the ambient temperature is less than or equal to 0°C, drainpipes and water
refill pipes may freeze and thereby be blocked or crack. Take anti-freezing
measures for the pipes.
Issue 03 (2022-11-25)
Take a pipe connector out of the fitting bag, and secure one end of the pipe
connector to the spray drainpipe port reserved on the unit to a torque of 60
N·m using an 18'' adjustable torque wrench.
Connect the spray drainpipe to the other end of the pipe connector.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installing Pipes
20