Huawei FusionCol8000-E260 Quick Manual page 85

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E260:
Table of Contents

Advertisement

FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (Building Scenario)
Figure 11-5 Teamwork Settings
Step 2 Set teamwork parameters.
Set parameters on the master unit (with the smallest address) first. All teamwork
parameters can be set on the master unit. Only Teamwork group num, System
address, Enable teamwork CAN resistor, Teamwork function, Networking
mode, and Teamwork parameter synchronization can be set on slave units.
Other parameters of the slave units will be modified by the master unit
synchronously.
Parameter
Teamwork group num
System address
Networking mode
Enable teamwork CAN
resistor
Teamwork function
Issue 03 (2022-11-25)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the networking mode for teamwork control.
The networking mode selected on the screen must
match the actual networking mode. Otherwise, the
teamwork function is unavailable.
If CAN network is selected, set Enable teamwork
CAN resistor to Yes for the first and last units. If
Enable teamwork CAN resistor is set to No for the
first and last units, the CAN communication quality
will be affected, and even the teamwork CAN
networking will fail.
Yes: The teamwork control CAN resistor is enabled
for the unit.
No: The teamwork control CAN resistor is disabled
for the unit.
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
11 Power-On Commissioning
78