FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (Building Scenario)
Figure 3-1 Positions of the corner fittings of the unit
When marking the positions for corner fittings, ensure that the four lines form a
rectangle.
Step 4 Place the shock absorption pads at the corresponding positions of corner fittings
on the concrete platforms.
Step 5 Adjust the unit in the required direction, connect the steel hoisting ropes, and
hoist the unit onto the concrete platforms.
● When hoisting the unit, ensure that the four corner fittings of the unit are
aligned with the marked mounting positions for corner fittings on the concrete
platforms.
● When hoisting the unit, prevent the unit from being scratched by steel ropes.
Issue 03 (2022-11-25)
NO TICE
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installing a Unit
10