FusionCol8000-E260 Modular Indirect Evaporative
Cooling System
Quick Guide (Building Scenario)
Step 4 Follow the onscreen instructions to complete the wizard-based startup.
1.
2.
Issue 03 (2022-11-25)
Figure 11-16 Checking before startup
Select the items that are involved in wizard-based startup (all items are
selected by default when you access the commissioning item selection screen
for the first time) and confirm whether to start the task.
Tap Yes to start the system and commission components.
Tap No to exit the commissioning while keeping the system shut down.
Figure 11-17 Wizard Startup
NO TE
After a component is commissioned successfully, the system automatically proceeds
with the next component you selected. Please wait during the commissioning.
Check the commissioning result.
If the message "Commissioning succeeded" is displayed in the lower left
corner, tap Confirm. The home screen is displayed.
If the message "Commissioning failed" is displayed in the lower left
corner:
i.
Click the link at "Commissioning failed" to view the failure cause, tap
Back and Confirm, and troubleshoot based on the failure cause.
ii.
On the home screen, choose Maint > Wizard Startup and perform
commissioning again.
Copyright © Huawei Digital Power Technologies Co., Ltd.
11 Power-On Commissioning
94