7 Installation
Fig.82
Maximum length of the connections
130 - 150 kW
L
L
5
6
Tab.32
Maximum length for configuration C
Configuration
Unit
mm
5
m
6
m
7
m
8
m
Fig.83
Maximum length of the connections
L1
9
Tab.33
Maximum length for configuration C
Configuration
Unit
mm
9
m
7.6

Electrical connections

66
IX
L
L
7
8
33
IX 245–130
Ø 110
L < 8
L < 8
L < 6
L < 7
L2
53
IX 245–130
Ø 110
(L1 + L2) max = 20
(L1 max) = 10
200 - 250 kW
L
5
IX 245–150
Ø 110
L < 8
L < 8
L < 6
L < 7
Configuration C
53
Important
Pipes subject to technical evaluation 14 08–1289.
IX 245–150
Ø 110
(L1 + L2) max = 20
(L1 max) = 10
7.6.1

Recommendations

Only qualified professionals may carry out electrical connections, always
with the power off.
Earth the appliance before making any electrical connections.
France: Earthing must comply with the NFC 15-100 standard.
Power the appliance via a circuit that includes an omni-polar switch with
contact opening distance of 3 mm or more.
When making electrical connections to the mains, respect the polarities.
L
L
7
6
IX 245–200
IX 245–250
Ø 160
Ø 160
L < 20
L < 11
L < 22
L < 12
L < 16
L < 6
L < 20
L < 9
IX 245–200
IX 245–250
Ø 160
Ø 160
(L1 + L2) max = 42
(L1 + L2) max = 21
7702684 - v04 - 05092019