PROFIBUS PA profile structure
D.7 Device/input simulation
D.7
Device/input simulation
You can define a simulated value to be input to the AIFB instead of the output value from the
Transducer Block. The simulated value allows the AIFB to be tested independently of the
characteristics of the environment.
Actual Mode: Device / Output Simulation
Actual Mode allows you to select one of three possible outputs.
Actual Mode
(2.6.2.)
AUTO
MAN
O/S
D.8
AIFB function groups
D.9
Analog Input Function Block function groups (simulation, mode
and status)
Measured values are processed within an Analog Input Function Block to produce the device
output. See AIFB function groups (Page 198). The output is communicated via cyclic transfer
to PROFIBUS PA and displayed on the LCD.
198
Description
automatic
manual
function block disabled
Output value
the automatically-recorded measured value
a manually-set fixed simulation value
the preset safety value.
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF