Fail-Safe Mode (2.6.9.) - Siemens SITRANS L Operating Instructions Manual

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Decimal point (2.6.8.4.)
Factory setting:
Setting range:
Purpose:
7.3.6.9

Fail-safe mode (2.6.9.)

Mode (2.6.9.1.)
Factory setting:
Setting range:
Purpose:
Value (2.6.9.2.)
Note
Mode (2.6.9.1.) (Page 115) must be set to SUB VALUE before this parameter can be defined.
Factory setting:
Setting range:
Purpose:
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
2
Range: 0, 1, 2, 3, 4, 5, 6, 7
The number of digits to display after the decimal point.
(The LCD is limited to displaying two decimal places in Measurement mode.
In SIMATIC PDM, up to seven decimal places may be used to display meas-
ured values.)
LAST VALUE
SUB VALUE
Substitute value.
Value (2.6.9.2.) (Page 115) used as output value.
LAST VALUE
Last value. (Store last valid output value).
USE BAD VALUE
Use bad value. (Calculated output value is incor-
rect).
Fail-safe Mode occurs if the status of the input value is bad, or if the device
has been put into Fail-safe mode using Simulation.
Mode defines the material level to be reported when the LOE (Loss of Echo)
timer expires.
0
Range: -999999 to 999999
User-defined default for the Output Value, if sensor or sensor electronic
fault is detected. Units are defined in Unit (2.6.8.2.) (Page 114).
Parameter assignment
7.3 Setup (2.)
115