Siemens SITRANS L Operating Instructions Manual page 98

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Parameter assignment
7.3 Setup (2.)
Empty rate/min (2.3.8.3.)
Empty rate defines the maximum rate at which the reported sensor value
increase. Allows you to adjust the device's response to increases in the actual material level.
Empty rate is automatically updated whenever Response rate (2.3.8.1.) (Page 97) is altered.
Note
Enter a value slightly greater than the maximum vessel-emptying rate, in units per minute.
Response rate (2.3.8.1.) (Page 97)
Options
Range
Related parameters
The value produced by the echo processing which represents the distance from sensor
1)
reference point to the target.
98
slow (factory setting)
medium
fast
0 to 99999 m / min.
Level unit (2.3.2.) (Page 93)
is allowed to
1)
Empty rate
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr200

Table of Contents