Parameter assignment
7.3 Setup (2.)
Vessel shape
Linearization Table must be selected in order for level/volume values to be transferred. For
more detail, refer to XY index (2.4.1.5.) (Page 101).
7.3.4.3

Maximum volume (2.4.1.2.)

Description
Values
Factory setting
Related
parameters
For readings in volumetric units instead of percentage values:
1. Select a volumetric unit from PV Units (volume/level) (2.3.3.).
2. Enter the vessel volume corresponding to High Calibration Point.
100
LCD Display/
description
HALF SPHERE BOTTOM
FLAT SLOPED BOTTOM
PARABOLIC ENDS
Parabolic end horizontal
cylinder
LINEAR TABLE
Linearization table (lev-
el/volume/breakpoints)
The maximum volume of the vessel. Enter the vessel volume corresponding to
High Calibration Point. For example, if your maximum vessel volume is 8000 L,
enter a value of 8000. Volume units are defined by the user but are not explicitly
stated in the device.
Range: 0.0000 to 99999
100.0
Low calibration point (2.3.7.1.) (Page 95)
High calibration point (2.3.7.2.) (Page 95)
Vessel shape (2.4.1.1.) (Page 99)
Also required
maximum volume, dimension A
maximum volume, dimension A
maximum volume, dimension A,
dimension L
maximum volume, tables 1-32
1)
level and volume breakpoints
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF