Time In Operation (4.2.2.); Remaining Lifetime (4.2.3.); Reminder Activation (4.2.4.); Reminder 1 (Required) (4.2.5.) - Siemens SITRANS L Operating Instructions Manual

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Parameter assignment
7.5 Service (4.)
7.5.2.2

Time in operation (4.2.2.)

Read only. The amount of time the sensor has been operating.
7.5.2.3

Remaining lifetime (4.2.3.)

Read only. Lifetime expected (4.2.1.) (Page 123) less Time in operation (4.2.2.) (Page 124).
7.5.2.4

Reminder activation (4.2.4.)

Factory setting:
Setting range:
Purpose:
Description:
7.5.2.5

Reminder 1 (required) (4.2.5.)

Factory setting:
Setting range:
Purpose:
Description:
7.5.2.6

Reminder 2 (demanded) (4.2.6.)

Factory setting:
Setting range:
Purpose:
Description:
7.5.2.7

Maintenance status (4.2.7.)

Indicates which level of maintenance reminder is active.
In SIMATIC PDM, open the menu Diagnostics > Device Diagnostics, click on the
Maintenance tab, and check the Calibration Schedule Status window.
124
OFF
Reminder 1 (Maintenance Required), Reminder 2 (Maintenance Demanded),
Reminders 1 and 2, OFF
Allows you to enable a maintenance reminder.
To modify this parameter via SIMATIC PDM:
Go to menu Device – Maintenance.
0.164 years
0 to 20 years
If Remaining lifetime (4.2.3.) (Page 124) is equal to or less than this value,
the device generates a Maintenance Required reminder.
1. Modify values as required.
2. Set Reminder activation (4.2.4.) (Page 124) to the desired option.
0.019 years
0 to 20 years
If Remaining lifetime (4.2.3.) (Page 124) is equal to or less than this value,
the device generates a Maintenance Demanded reminder.
1. Modify values as required.
2. Set Reminder activation (4.2.4.) (Page 124) to the desired option.
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF