Diagnosing and troubleshooting
9.2 General fault codes
Code/
Meaning
Icon
S:10
Input parameters Low Calibration Point (1.6.)
and High Calibration Point (1.7.) are the same.
S: 11
Internal temperature sensor failure.
S: 12
Internal temperature of device has exceeded
specifications: it is operating outside its tem-
perature range.
S:14
Input Scaling (2.6.5.) Upper and lower values
for AIFB1 are the same.
S:15
Input Scaling (2.6.5.) Upper and lower values
for AIFB2 are the same.
S: 17
Calibration interval as defined in Maintenance
Required Limit has expired.
S: 18
Calibration interval as defined in Maintenance
Demanded Limit has expired.
S: 28
*
Internal device failure caused by a RAM
memory error.
S: 29
*
EEPROM damaged.
S: 31
*
Flash error.
S: 32
*
IDENT number conflict.
S: 33
*
Factory calibration for the internal temperature
sensor has been lost.
144
Corrective Action
Check calibration settings of device.
Ensure settings for High Calibration Point and Low
Calibration Point are different.
Repair required: contact your local Siemens representa-
tive.
Relocate device and/or lower process temperature
enough to cool device.
Inspect for heat-related damage and contact your local
Siemens representative if repair is required.
Fault code will persist until a manual reset is per-
formed using SIMATIC PDM or the LCD interface.
Check configuration for AIFB1
Ensure that Upper Value and Lower Value (Input Scal-
ing) are not the same.
Check configuration for AIFB2.
Ensure that Upper Value and Lower Value (Input Scal-
ing) are not the same.
Perform calibration.
Perform calibration.
Replacement required: contact your local Siemens repre-
sentative.
Replacement required: contact your local Siemens repre-
sentative
Replacement required: contact your local Siemens repre-
sentative
Ensure value of the Ident number selector is correct for
the network configuration. If it is correct, the device needs
to be re-parameterized by the PLC.
Replacement required: contact your local Siemens repre-
sentative
Operating Instructions, 07/2021, A5E32337680-AF