Diagnosing and troubleshooting
9.4 Operation troubleshooting
Symptom
Reading response slow Fill rate/min (2.3.8.2.) (Page 97)
Reads correctly but
occasionally reads high
when vessel is not full
Level reading lower
than actual material
level
148
Cause
liquid surface vortexed
material filling
setting incorrect
detecting close range echo
build up near top of vessel or
nozzle
nozzle problem
material is within Near Range
zone
multiple echoes processed
vessel near empty and low dK
material
Action
decrease Fill rate/min (2.3.8.2.) (Page 97)
relocate device to side pipe
increase confidence threshold in Echo threshold (2.5.7.3.)
(Page 105)
relocate SITRANS LR200
increase measurement response if possible
clean the antenna
use Auto false echo suppression (2.5.10.1.) (Page 107) and
Auto false echo suppression range (2.5.10.2.) (Page 109)
decrease Near range (2.5.1.) (Page 102) (minimum value
depends on antenna type)
raise SITRANS LR200
ensure Algorithm (2.5.7.1.) (Page 104) is set to F (First
echo)
ensure Material (1.2.) selection is LIQUID LOW DK
set Position detect (2.5.7.2.) (Page 104) to Hybrid
set CLEF range (2.5.7.4.) (Page 105) to 0.5 m
Operating Instructions, 07/2021, A5E32337680-AF