Condensed Status - Siemens SITRANS L Operating Instructions Manual

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

E.14

Condensed status

These codes are available when Condensed Status is enabled. See Condensed Status (3.4.)
for more details.
Hex value
0x80
0x84
0x86
0x80
...0x8E
0xA0
...0xA3
0xA4
...0xA7
0xA8
...0xAB
0xBC
...0xBF
Hex value
0x45
0x4F
0x68
...0x6B
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
Condensed Status (GOOD)
Status - GOOD
Description
GOOD – ok
No error or special condition is associated with this value.
GOOD – update event
Set if the value is good and the block has an active Update
event. (This status remains active for 20 seconds.)
GOOD – active adviso-
Set if the value is good and the block has an active Alarm.
ry alarm
GOOD – limit check/
See Status Codes for Good Quality (Page 204).
update event
GOOD – initiate fail
This fault is not generated by the product, but can be simu-
safe
lated.
GOOD – maintenance
Value is valid. Maintenance is recommended within a medi-
required
um-term period.
GOOD – maintenance
Value is valid. Maintenance is demanded within a short- term
demanded
period.
GOOD – function
Device performs internal function check without influencing
check
the process. Value is valid.
Condensed Status (UNCERTAIN)
Status - UNCERTAIN
Description
UNCERTAIN – substi-
Output of Failsafe logic only.
tute set
UNCERTAIN – initial
Default value as long as no measured value is available or
value
until a diagnosis is made that affects the value and the status
accorded to it.
UNCERTAIN – mainte-
Usability of the process value depends on the application.
nance
Value is potentially invalid. Cause can be determined by read-
demanded
ing the extended diagnostics
within a short-term period.
PROFIBUS communication
E.14 Condensed status
. Maintenance is demanded
a)
205