6.3 Remote operation
In Step 5 – Summary, check parameter values. Click on BACK to return and revise values,
FINISH to save settings offline, or FINISH AND DOWNLOAD to save settings offline and
transfer them to the device.
The message Quick Start was successful will appear. Click on OK.
6.3.4.9

Configuring a stillpipe application

• Launch the Quick Start wizard and follow steps 1 to 2.
• In step 2, select Application Type – Level in a vessel with stillpipe, Material – Liquid
Low dK, and set the stillpipe diameter as desired.
• The wizard updates the propagation factor according to the pipe diameter, and enables
the CLEF algorithm for low dK liquids [see Propagation factor (2.5.3.) (Page 103) for more
detail].
• Continue through steps 3 to 5 then click on FINISH AND DOWNLOAD to save settings
offline and transfer them to the device.
64
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF