Bosch Rexroth IndraControl S20 System And Installation Manual page 96

Hide thumbs Also See for Rexroth IndraControl S20:
Table of Contents

Advertisement

94/122
Bosch Rexroth AG
Technical data and ordering data
General data (standard values; for deviations see module-specific documentation) [...]
Protection class
Air clearances and creepage distances
Housing material
Pollution degree
Overvoltage category
Mechanical tests (standard values; for deviations see module-specific documentation)
Vibration resistance according to EN 60068-2-6/IEC 60068-2-
6
Shock test according to EN 60068-2-27/IEC 60068-2-27
Bump endurance test according to EN 60068-2-27/IEC
60068-2-27
Conformance with EMC Directive 2014/30/EU
(for deviations and detailed values see module-specific documentation)
Noise immunity test according to EN 61000-6-2
Electrostatic discharge (ESD), EN 61000-4-2/IEC 61000-4-2
Electromagnetic fields, EN 61000-4-3/IEC 61000-4-3
Fast transients (burst), EN 61000-4-4/IEC 61000-4-4
Transient surge voltage (surge), EN 61000-4-5/EN 61000-4-5 Criterion B
Conducted interference, EN 61000-4-6/IEC 61000-4-6
Noise emission test according to EN 61000-6-3
Radio disturbance characteristics, EN 55022
Low-voltage modules: developed according to IEC 61850-3
(for deviations and detailed values see module-specific documentation)
Electrostatic discharge (ESD), EN 61000-4-2/IEC 61000-4-2
Electromagnetic fields, EN 61000-4-3/IEC 61000-4-3
Fast transients (burst), EN 61000-4-4/IEC 61000-4-4
Transient surge voltage, EN 61000-4-5/IEC 61000-4-5
Conducted interference, EN 61000-4-6/IEC 61000-4-6
Immunity against magnetic fields, EN 61000-4-8/IEC 61000-4-
8
Immunity against attenuated oscillating magnetic fields,
EN 61000-4-10/IEC 61000-4-10
Immunity to conducted common mode interference,
EN 61000-4-16/IEC 61000-4-16
Attenuated oscillating waves, EN 61000-4-18/IEC 61000-4-18 1 kV symmetrical, 2.5 kV asymmetrical
Radio disturbance characteristics, EN 55022
DOK-CONTRL-S20*SYS*INS-AP02-EN-P
IndraControl S20 System and Installation
Low-level signal: III, IEC 61140, EN 61140, VDE 0140-1
Low voltage, mounted in an adequate housing with at least
IP54 degree of protection: II, IEC 61140, EN 61140, VDE
0140-1
Low-level signal: according to EN 60664-1
Low voltage: according to EN 61010-2-201
Plastic
Low-level signal: 2, EN 60664-1
Low voltage: 2, EN 61010-1
Low-level signal: II, EN 60664-1
Low voltage: III, EN 61010-1
5g
30g
10g
Criterion B
Criterion A
Criterion B
Criterion A
Class B
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
300 A/m continuous, 1000 A/m for 1 s
100 A/m
30 V continuous, 300 V for 1 s
Class B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents