Huawei UPS5000-H-400K-FT Manual page 90

Hide thumbs Also See for UPS5000-H-400K-FT:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)-FT
User Manual (100 kVA Power Module)
Figure 4-1 Clearances
Table 4-1 Dimensions description
Configuration
400K–600K: top cable routing, rear air
exhaust
400K–600K: bottom cable routing, rear air
exhaust
400K–600K: top cable routing, top air
exhaust
Issue 03 (2022-11-29)
Reserve a clearance of at least 500 mm from the top of the cabinet for
operations.
Reserve a clearance of at least 500 mm from the rear of the cabinet for
ventilation.
Reserve a clearance of at least 800 mm if you need to perform operations
at the rear of the cabinet.
If the top air-flow model is configured, no clearance needs to be reserved
at the rear.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Dimensions (Unit: mm)
H
W
2000
800
2200
1200
2350
800
b
500
500
0
82

Advertisement

Table of Contents
loading

Table of Contents