Huawei UPS5000-H-400K-FT Manual page 160

Hide thumbs Also See for UPS5000-H-400K-FT:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)-FT
User Manual (100 kVA Power Module)
Choose Monitoring > Wireless Module > Running Information on the WebUI.
Check the 4G module running status, confirm that the 4G module dial-up is
successful, and check the signal strength.
Step 3 Set and test domain name parameters.
1.
2.
Step 4 Connect the device on the NetEco app.
----End
FE Access Scenario (LCD)
Step 1 Set iManager-M Service parameters and the IP addresses for the DNS server.
Choose System Info. > Settings > Settings Wizard on the LCD. On the iManager-
M Service screen:
Step 2 Set the IP address of the device.
Choose System Info. > Settings > Settings Wizard on the LCD. On the Network
Param. page, set the IP address, subnet mask, and gateway based on site
requirements.
Step 3 Connect the device on the NetEco app.
----End
FE Access Scenario (WebUI)
Step 1 Set the IP address of the device.
Choose System Settings > Comm. Settings > IP Settings on the WebUI. Set the
IP address type to IPv4, and set the IP address, subnet mask, and default gateway
based on site requirements.
Step 2 Set IP addresses for the DNS server.
Choose System Settings > Comm. Settings > DNS Server Address on the WebUI.
Set IP addresses for the DNS server based on site requirements.
Step 3 Set and test domain name parameters.
1.
Issue 03 (2022-11-29)
Choose System Settings > NMS Application > BIN > Communication
Parameters on the WebUI. Set parameters as follows:
Address type: Domain name
Server domain name and Port number: Retain the default values.
Connection test link setup port: 4G
Click Test Connect. After the test is successful, click Submit.
Set Enable/Disable to Enable and Access channel to FE
Set IP addresses for the DNS server based on site requirements.
Choose System Settings > NMS Application > BIN > Communication
Parameters on the WebUI. Set parameters as follows:
Address type: Domain name
Server domain name and Port number: Retain the default values.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Single UPS Commissioning
152

Advertisement

Table of Contents
loading

Table of Contents