Huawei UPS5000-H-400K-FT Manual page 35

Hide thumbs Also See for UPS5000-H-400K-FT:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)-FT
User Manual (100 kVA Power Module)
Figure 2-3 Typical application scenario of 1+1 parallel system
Dual-Bus System
A dual-bus system consists of two independent UPS systems. Each UPS system
consists of one UPS or multiple UPSs connected in parallel. Of the two UPS
systems, one is the master system and the other is the slave system. The dual-bus
system is highly reliable and is suitable for loads with multiple input terminals. An
optional static transfer switch (STS) can be installed to start the bus
synchronization controller (BSC). The UPS systems work in inverter mode or
bypass mode.
Issue 03 (2022-11-29)
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Product Overview
27