Huawei UPS5000-H-400K-FT Manual page 174

Hide thumbs Also See for UPS5000-H-400K-FT:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)-FT
User Manual (100 kVA Power Module)
Parameter
Peak shaving rule
configuration
mode
Battery power
percentage in
discharge period
1/2/3/4/5/6 (%)
Peak shaving
discharge start
time 1/2/3/4/5/6
Peak shaving
discharge end time
1/2/3/4/5/6
Peak shaving
charge start time
1/2/3/4/5/6
Issue 03 (2022-11-29)
Description
Easy: You can configure the
following parameters on the
UI to implement peak
shaving. This mode supports
only the configured rules.
Importing Configurations:
You can set only Normal
backup time reserved for
peak shaving (min) and SOC
threshold to exit peak
shaving (%). Choose
Maintenance > Import Peak
Shaving. and import a
configuration file to
configure the rules for peak
shaving based on the day,
month, or week mode.
Specifies the percentage of
the rated power provided by
batteries during a discharge
period. The remaining part of
power is provided by the
mains.
Specifies the start time and
end time of proactive battery
discharge during peak hours.
NOTICE
A maximum of six discharge
periods are supported in a day.
The following conditions must
be met. Otherwise, the system
cannot enter the peak shaving
mode.
● The start time of the current
period must be earlier than
the end time.
● The current period must not
overlap with other periods.
Specifies the start time and
end time of battery charge
during off-peak hours.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Single UPS Commissioning
Default Value
Value Range
Easy
Importing Configurations,
Easy
0.0
0.0–15.0
00:00:00
00:00:00–23:59:59
00:00:00
00:00:00–23:59:59
00:00:00
00:00:00–23:59:59
166