SiUS30-1301
3.7.2 Cool/Heat Mode Switching (Heating and Simultaneous Cooling/Heating
Operation Connection)
Set Cool/Heat Separately for Each Branch Selector Unit by Cool/Heat Selector.
(1) Before turning ON the power of the Branch Selector unit, set the DIP switch (DS1-1) on the Branch Selector unit PCB as
following.
(2) Then, connect the COOL/HEAT selector to the terminal A, B and C of the terminal block X1M on the Branch Selector
unit PCB.
This setting is read into the micro-computer when turning ON the power supply.
Be sure to make the setting before turning ON the power supply.
Be sure to close the Electrical Components Box lid after setting.
Example of transmission line connection
Example of connecting transmission wiring.
Connect the transmission wirings as shown in the Fig. 1.
Condensing unit
TO IN/D UNIT TO OUT/D UNIT
F1 F2
F1 F2
A
B
F1
F2
F1
F2
IN/D
OUT/D.BS
C
Branch Selector unit A
F1
F2
F2
F1
Field Setting
1
2
ON
OFF
DS1
Branch wiring
Use 2-core wires.
(There is no polarity.)
F1
F2
F1
F2
CON.B.S.
IN/D
Branch Selector unit B
F1
F2
COOL/HEAT
selector
X1M
A B C
COOL/HEAT selector
In case of the indoor unit connect as the cool only unit, it wire
the terminal
of the last Branch Selector unit.
F1
F2
OUT/D.BS
F1
F2
F1
F2
IN/D
OUT/D.BS
Final Branch Selector unit
To the indoor unit where
the selection of heating
and cooling is available.
Cool/heat selector remote
control wiring
Use 3-core wires.
(Keep in mind the polarity.)
A
B
F1
F2
IN/D
C
Final Branch Selector unit
F1
COOL/HEAT
selector
Fig. 1
Field Setting from Condensing Unit
F1 F2
Final unit
1st unit
Cooling Only
A
B
F1
F2
CON.B.S.
C
F1
F1
F2
COOL/HEAT
selector
Indoor unit for cooling
Note:
F1 F2
F2
F2
119