Field Setting from Remote Controller
2.4.2 Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
First Code
Mode No.
No.
10 (20)
0
 FXTQ
Mode No.
First Code No.
10 (20)
0
Ultra Long Life Filter Sign Setting
When a Ultra long life filter is installed, the filter sign timer setting must be changed.
Mode No.
First Code No.
10 (20)
1
 FXTQ
Mode No.
First Code No.
10 (20)
1
Selection of Thermistor
Select the thermistor to control room temperature.
Mode No.
First Code No.
10 (20)
2
The factory setting for the Second Code No. is "01" and room temperature is controlled by the indoor unit suction air
thermistor and room temperature thermistor in remote controller.
When the Second Code No. is set to "02", room temperature is controlled by the suction air thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the room temperature thermistor in remote
controller.
94
Second
Standard
Long Life
Code No.
Filter
01
200 hrs.
2,500 hrs.
02
100 hrs.
1,250 hrs.
Second Code No.
01
02
Second Code No.
01
02
Second Code No.
01
02
Second Code No.
01
02
03
Ultra Long Life
Filter
Filter
10,000 hrs.
5,000 hrs.
Setting
Low
High
Setting
Long Life Filter
Ultra Long Life Filter
Setting
Display time: 2,500/1,250
Display time: 10,000/5,000
Thermistor that controls room temperature
Room temperature thermistor in remote
controller and suction air thermistor for indoor
unit
Suction air thermistor for indoor unit
Room temperature thermistor in remote
controller
Setting
Contamination Light
Contamination Heavy
SiUS30-1301
Field Setting