Field Setting from Remote Controller
 In the Case of FXFQ36
First code
Mode No.
No.
13 (23)
0
Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when optional air outlet blocking pad has been
installed.) The second code No. is factory setting to "01."
Mode No.
First Code No.
13 (23)
1
Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Mode No.
First Code No.
13 (23)
4
Some indoor unit models are not equipped with draft prevention (upward) function.
Setting of the Static Pressure Selection (for FXDQ model)
Setting of Humidifier / Air Purifier Fan Tap (for FXTQ model)
Residual Operation Time (for FXTQ model)
98
Second
Setting
code No.
01
Standard (N)
02
High Ceiling (H)
03
Higher Ceiling (S)
Second Code No.
01
02
03
Second Code No.
01
02
03
Model No.
First Code No.
13 (23)
5
Mode No.
First Code No.
14 (24)
4
Mode No.
First Code No.
14 (24)
5
Ceiling height
4-way Outlets 3-way Outlets 2-way Outlets
Lower than
Lower than
10-1/2 ft
11-12/18 ft
Lower than
Lower than
11-12/18 ft
13-1/8 ft
Lower than
Lower than
13-25/32 ft
13-25/32 ft
Setting
F: 4-direction airflow
T: 3-direction airflow
W: 2-direction airflow
Setting
Upward (Draft prevention)
Standard
Downward (Ceiling soiling prevention)
Second Code No.
01
02
Second Code No.
01
02
Second Code No.
01
02
03
SiUS30-1301
Lower than
13-25/32 ft
Lower than
13-25/32 ft
External static pressure
Standard (0.002 psi)
High static pressure (0.006 psi)
Setting
Remote controller setting
H tap
Setting
30 seconds
60 seconds
120 seconds
Field Setting