INSTALLATION MANUAL System air conditioner English MODEL RWEYQ72PTJU RWEYQ84PTJU Français RWEYQ144PTJU RWEYQ168PTJU Español RWEYQ216PTJU RWEYQ252PTJU Read these instructions carefully before installation. Keep this manual in a handy place for future reference. This manual should be left with the equipment owner.
Page 3
[Heat pump system] [Heat recovery system] F2 Q1 Q2 F2 Q1 Q2 A B C A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F2 F1 F2 Q1 Q2 C/H SELECTOR TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT C/H SELECTOR TO IN/D UNIT TO OUT/D UNIT TO MULTI UNIT F1 F2...
Page 4
TO IN/D UNIT A B C A B C F1 F2 P1 P2 P1 P2 figure 16 figure 17 figure 18 [Heat pump system] ∗6 [Heat recovery system] [13] ∗17 figure 19 figure 20 [A-arrow view] [B-arrow view] figure 21 figure 22 (Fig.
RWEYQ72PTJU RWEYQ168PTJU RWEYQ84PTJU RWEYQ216PTJU Installation manual VRV-WIII System air conditioner RWEYQ144PTJU RWEYQ252PTJU CAUTION ....Indicates a potentially hazardous situation CONTENTS which, if not avoided, may result in minor or moderate injury. It may also be used to 1. SAFETY CONSIDERATIONS............1 alert against unsafe practices.
Page 7
Instruct the customer to keep the area around the unit ified by Daikin are used, fire or explosion may occur. clean. CAUTION NOTE •...
(Check by removing the front panel.) RWEYQ-P series. These units are designed for indoor installation and used for cooling and heatpump applications. Accessory pipes Name The RWEYQ-P units can be combined with Daikin VRV series indoor For discharge For suction For suction Clamp (A) Clamp (B) units for air conditioning purposes.
SELECTION OF LOCATION WARNING This unit does not have specifications for outdoor installation. The Do not install in the following locations. unit must be installed indoors (example: machine room, …). • Locations such as kitchens which contain a lot of mineral oil or steam Paying attention to the conditions mentioned below, select the place for in the atmosphere or where oil may splatter on the unit.
HANDLING OF THE BRAZED PLATE NOTE TYPE HEAT EXCHANGER • Prepare a water drainage channel around the foundation to con- densate waste water from around the unit. CAUTION • If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities first.
7-3 Daily service and maintenance [NOTES] (1) The circle marks in the columns for corrosion or scale to develop. Management of water quality (2) Corrosion has a tendency to occur when water temperature is high The plate type heat exchanger has a structure that does not permit (104 °F or more), and if metals with no protective coating whatever dismantling and cleaning, or replacing any parts.
FIELD WIRING 8-3 General • Make sure to connect the power source wire to the power source ter- minal block and to clamp it as shown in figure 8, chapter “Field line NOTE connection”. • All field wiring and components must be installed by a licensed elec- •...
Connect the wire to the terminal block on PC board with care since too 2. PC board (A1P) much pressure may cause breakage of the PC board. 3. Mount an insulation sleeve. Field line connection: transmission wiring, interlock circuit, pump oper- 4.
Field line connection: CAUTION L1, L2, L3, phase of the power supply wiring should be clamped to the 〉 〈Precautions when laying power wiring safety catch using the included clamp material. The green and yellow striped wrapped wires should be used for ground- Use round pressure terminals for connections to the power terminal ing.
REFRIGERANT PIPING • Incorrect installation may cause breakage of outside unit. (Refer to figure 23) 1. Caution nameplate CAUTION 2. Horizontal line 3. Ground After completing installation, be sure to open the valves. 4. Straight part of 19-11/16 in. or more (See 9-9 Additional refrigerant charge for details) (Operating the 5.
〈Cautions for installation of multiple outdoor units〉 Precautions when connecting pipes • See the following table for flare part machining dimensions. The piping between the outdoor units must be routed level or slightly • When connecting the flare nuts, apply refrigerant oil to the inside of upward to avoid the risk of oil detention to the piping side.
9-5 Example of connection ∗ In case of a system of switching between cooling and heating, all systems use 2-tube piping (for suction gas piping and liquid piping). No BS unit is required. English...
9-6 Air tight test and vacuum drying 9-8 Checking of device and installation conditions The units were checked for leaks by the manufacturer. Be sure to check the followings. Confirm that the valves are firmly closed before Air tight test or vacuum Make sure there is no faulty power wiring or loosing of a nut.
9-10 Stop valve operation procedure After the vacuum drying is finished, charge the additional refrigerant in its liquid state through the liquid stop valve service port. Taking CAUTION into account following instructions: • Check that gas and liquid stop valves are closed. Do not open the stop valve until 1-6 of “9-8 Checking of device and •...
10. CHECKS AFTER INSTALLATION (1) Check the connection of interlock The outside unit cannot be operated if the circuit interlock circuit has not been connected. WARNING (2)• As necessary, configure the system Always perform configuration after turning settings onsite by using the ON the power.
〈Cautions for check operation〉 11-4 Check of normal operation • If the system is started within about 12 minutes after the outdoor/ After the check operation is completed, operate the unit normally. (Heat- indoor units are turned ON, the compressor will not run and H2P ing is not possible if the outdoor temperature is 75 °F or higher.
Page 23
Dealing with the situations where the result exceeds the maximum concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system. Please consult your Daikin supplier. English...