Daikin VRV-WIII RWEYQ72PTJU Service Manual page 104

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

Field Setting from Remote Controller
External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the condensing. The input is performed from
the T1-T2 terminal of the operation terminal block in the electrical components box .
Mode No.
First Code No.
12 (22)
1
Thermostat Switching
Differential value during thermostat ON/OFF control can be changed.
Mode No.
First Code No.
12(22)
2
Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
 When thermostat OFF airflow volume up mode is used, careful consideration is required before deciding installation
location.
Mode No.
First Code No.
12 (22)
3
Setting of Operation Mode to "AUTO"
This setting makes it possible to change differential values for mode selection while in automatic operation mode.
Mode No.
First Code No.
12 (22)
4
The automatic operation mode setting is made by the use of the "Operation Mode Selector" button.
96
F2 T1 T2
Forced stop
Input A
Second Code No.
ON: Forced stop (prohibition of using the
01
remote controller)
OFF: Permission of using the remote controller
OFF  ON: Permission of operation
02
ON  OFF: Stop
ON: Operation
OFF: The system stops, then the applicable
03
unit indicates "A0". The other indoor units
indicate "U9".
Second Code No.
01
02
Second Code No.
01
02
Second Code No.
01
02
03
0°F
1.8°F
3.6°F
Operation by input of the signal A
Differential value
1.8°F
0.9°F
Setting
LL airflow
Preset airflow
04
05
06
5.4°F
7.2°F
9.0°F
10.8°F 12.6°F
SiUS30-1301
07
08
Field Setting