SiUS30-1301
Image of operation in the case of A
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
40 % of rated power consumption
Forced thermostat OFF
(Fan operation)
Image of operation in the case of B
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
Image of operation in the case of A and B
Power consumption
Rated power consumption
80 % of rated power consumption
70 % of rated power consumption
60 % of rated power consumption
40 % of rated power consumption
Forced thermostat OFF
(Fan operation)
Field Setting
Demand level 1 instructing
Power consumption set by
"Demand 1 level setting".
The power consumption set with "Demand 1 level setting".
The power consumption set with "Demand 1 level setting".
Field Setting from Condensing Unit
Demand level 2 instructing Demand level 3 instructing
Demand level 2 instructing Demand level 3 instructing
The power
consumption during
the demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70 % of rated
power consumption"
has been set at
factory.)
When the "Normal
demand setting" is set
to ON ("OFF" has been
set at factory.), the
power consumption can
be set with the
"Demand 1 level
setting". ("70 % of rated
power consumption"
has been set at
factory.)
The power
consumption can
be set with the
"Demand 1 level
setting". ("70 % of
rated power
consumption" has
been set at
factory.)
During continuous demand operation,
when the external demand instruction is
received repeatedly, the instruction with
higher demand level has the precedence.
121