Stop; Stopping Operation - Daikin VRV-WIII RWEYQ72PTJU Service Manual

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

Stop

2. Stop

2.1

Stopping Operation

This operation defines the operation of the actuator while the system stops.
2.1.1 When System is in Stop Mode
Parts Name
Inverter compressor
Inverter cooling fan
Four-way valve (Main)
Four-way valve (Sub)
Electronic expansion valve (Main)
Electronic expansion valve (Subcooling)
Solenoid valve (Hot gas)
Solenoid valve (Oil return of water heat exchanger)
Solenoid valve (Receiver gas charging)
Solenoid valve (Receiver gas discharging)
Solenoid valve (Non-operating unit liquid pipe closing)
Branch Selector unit
2.1.2 Stopping Operation of Slave Units During Master Unit is in Operation
with Multi Condensing Unit System
This operation makes adjustments of required refrigerant amount with non-operating slave units
while the master unit is in operation.
 Cooling
The system operates in mode A or mode B listed in the table below.
Parts Name
Inverter compressor
Inverter cooling fan
Four-way valve (Main)
Four-way valve (Sub)
Electronic expansion valve (Main)
Electronic expansion valve (Subcooling)
Solenoid valve (Hot gas)
Solenoid valve (Oil return of water heat
exchanger)
Solenoid valve (Receiver gas charging)
Solenoid valve (Receiver gas
discharging)
Solenoid valve (Non-operating unit liquid
pipe closing)
Mode transition conditions
Ending conditions
Note:
∗1 Mode A or B operation
The changeover operation for mode A and B is performed for the reason that the required
refrigerant amount varies depending on the indoor unit operation capacity.
44
Symbol
20S1
20S2
EV1
EV3
SVP
SVE
SVL
SVG
SVSL
Mode A: Master unit collects refrigerant.
Mode B: Slave unit storage refrigerant.
Symbol
Electric Symbol
M1C
M1F, M2F
20S1
Y5S
20S2
Y7S
EV1
Y1E
EV3
Y3E
SVP
Y1S
SVE
Y2S
SVL
Y3S
SVG
Y4S
SVSL
Y6S
Electric Symbol
Mode A Operation (1)
M1C
OFF
M1F, M2F
OFF
Y5S
Holding
Y7S
Holding
Y1E
150 to 300 pulse
Y3E
0 pulse
Y1S
OFF
Y2S
Y3S
OFF
Y4S
OFF
Y6S
OFF
To Mode B when no
refrigerant shortage signal
is sent from indoor unit
Slave units are required to operate.
Master
unit
Actuator Function
OFF
OFF
Holding
Holding
0 pulse
0 pulse
OFF
OFF
OFF
OFF
ON
Indoor unit thermostat ON
Mode B Operation (1)
ON
To Mode A when
refrigerant shortage signal
is sent from indoor unit
Slave
unit
Function and Control
SiUS30-1301
OFF
OFF
Holding
Holding
0 pulse
0 pulse
OFF
OFF
OFF
OFF
ON