Humidification when Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction air temperature is 68°F or above and turns OFF the
humidifier if suction air temperature is 64°F or below when the heating thermostat is OFF.
Mode No.
First Code No.
15 (25)
1
Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries out residual operation for one
minute after the thermostat is stopped. (For the purpose of preventing dust on the air filter from falling off.)
Mode No.
First Code No.
15 (25)
2
Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit, this setting is
unnecessary.
Mode No.
First Code No.
15 (25)
3
Individual Setting of Ventilation
This is set to perform individual operation of Heat reclaim ventilator using the remote controller/central unit when Heat
reclaim ventilator is built in.
(Switch only when Heat reclaim ventilator is built in.)
Mode No.
First Code No.
15 (25)
5
Field Setting
Second Code No.
01
02
Second Code No.
01
02
With direct duct connection equipped with fan
Second Code No.
01
Interlocked operation between humidifier and
02
Second Code No.
01
02
Field Setting from Remote Controller
Setting
Setting of humidifier
Contents
Without direct duct connection
Contents
Individual operation of humidifier
drain pump
Contents
Individual operation of ventilation
99