7.1.2 Oil Return Operation in Heating or Cooling/Heating Simultaneous
Operation
Tc: High pressure equivalent saturation temperature
Te: Low pressure equivalent saturation temperature
[Starting conditions]
Start oil return operation in heating referring to the following conditions.
Cumulative compressor operating time after power supply turns ON exceeds 2 hours and the time
after the completion of previous oil return operation exceeds 8 hours. And cumulative oil return is
calculated based on Tc, Te compressor load.
Parts Name
Inverter compressor
Four way valve (Main)
Four way valve (Sub)
Electronic expansion
valve (Main)
Electronic expansion
valve (Subcooling)
Solenoid valve (Hot
gas)
Solenoid valve (Oil
return of water heat
exchanger)
Solenoid valve
(Receiver gas
charging)
Solenoid valve
(Receiver gas
discharging)
Solenoid valve (Non-
operating unit liquid
pipe closing)
Indoor unit fan
(Cooling)
Indoor unit electronic
expansion valve
(Cooling)
Indoor unit fan
(Heating)
Indoor unit electronic
expansion valve
(Heating)
Ending condition
Cooling Branch Selector unit
actuator
Electronic expansion valve (EVH)
Electronic expansion valve (EVL)
Electronic expansion valve (EVHS)
Electronic expansion valve (EVLS)
Electronic expansion valve (EVSC)
Function and Control
Electric
Symbol
Symbol
M1C
20S1
Y5S
20S2
Y7S
EV1
Y1E
EV3
Y3E
SVP
Y1S
SVE
Y2S
SVL
Y3S
Same as normal
heating operation
SVG
Y4S
SVSL
Y6S
M1F, M2F
EV
Y1E
M1F, M2F
EV
Y1E
Electric
Oil return operation
symbol
Y4E
600pulse
Y5E
760pulse (fully open)
Y2E
480pulse (fully open)
Y3E
480pulse (fully open)
Y1E
0pulse
During Oil Return
Preparation
Operation
104 Hz
OFF
OFF
2000 pulse
0 pulse
ON
OFF
OFF
OFF
ON
Thermostat ON/OFF:
Indoor unit control
Thermostat OFF:
OFF
320 pulse
OFF
320 pulse
2 minutes
Max. 8 minutes
Heating Branch Selector unit
actuator
Electronic expansion valve (EVH)
Electronic expansion valve (EVL)
Electronic expansion valve (EVHS)
Electronic expansion valve (EVLS)
Electronic expansion valve (EVSC)
Special Operation
After Oil Return
Operation
74 Hz
ON
Heat exchanger mode
Y7S = OFF: 2000 pulse
Y7S = ON : 180 pulse
0 pulse
ON
OFF
OFF
OFF
ON
Normal control
Normal control
Indoor unit control
Normal control
Max. 3 minutes
Electric
Oil return operation
symbol
Y4E
600pulse
Y5E
760pulse (fully open)
Y2E
480pulse (fully open)
Y3E
480pulse (fully open)
Y1E
0pulse
61