Setting Mode 2 - Daikin VRV-WIII RWEYQ72PTJU Service Manual

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

Field Setting from Condensing Unit
3.5

Setting Mode 2

Press and hold the MODE button
(BS1) for 5 seconds and set to

"setting mode 2".

<Selection of setting items>
Press the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
Press the RETURN button (BS3)
and decide the item. (The present
setting condition is blinked.)
<Selection of setting conditions>
Press the SET button (BS2) and set
to the setting condition you want.
Press the RETURN button (BS3)
and decide the condition.
Press the RETURN button (BS3)
and set to the initial status of "setting
mode 2".
Note:
∗ If you become unsure of how to proceed,
press the MODE button (BS1) and return
to setting mode 1.
108
No.
Setting Item
Cool/heat unified
1
address
2
demand address
Number of units for
4
sequential starting
Indoor unit forced
5
fan H
Indoor unit forced
6
operation
8
Te setting
9
Tc setting
12
Demand setting
13
AIRNET address
Additional refrigerant
20
charge operation
setting
Refrigerant
21
collection mode
setting
Interlock error
26
display setting
Power transistor
check mode
Check after
28
disconnection of
compressor wires
30
Demand setting 1
Normal demand
32
setting
Emergency
operation
(Setting for the main
38
unit operation
prohibition in multi
condensing unit
system)
Emergency
operation
(Setting for the slave
39
unit 1 operation
prohibition in multi
condensing unit
system)
Emergency
operation
(Setting for the slave
40
unit 2
operation prohibition
in multi condensing
unit system)
Description
Sets address for cool/heat unified operation.
Sets address for demand operation
Sets the number of units for sequential starting.
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
Allows forced operation of indoor unit.
Target evaporating temperature for cooling
Target condensing temperature for heating
Reception of demand signal
Sets address for AIRNET.
Carries out additional refrigerant charge operation.
Sets to refrigerant collection mode.
Sets interlock error display
Used for service diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PCB.
Changes target value of power consumption when demand
control 1 is input.
Normally enables demand control 1 without external input.
(Effective to prevent a problem that circuit breaker of small
capacity is shut down due to large load.)
Used to temporarily prohibit the applicable condensing unit
from operating should there be any defective part in multi
condensing unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.
SiUS30-1301
Field Setting