2. This unit cannot be installed outdoors. Install indoors (Machine room, etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RH Heat rejection from the casing : 0.64kW 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
Page 4
2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6 ~ 35°C), ~80%RH Heat rejection from the casing : 0.71kW 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
Page 5
2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RHHeat rejection from the casing : 0.64kW x 2 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
Page 6
2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RH Heat rejection from the casing : 0.71kW x 2 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
Page 7
2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RH Heat rejection from the casing : 0.64kW x 3 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
Page 8
2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F (1.6~35°C, ~80%RH Heat rejection from the casing : 0.71kW x 3 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
Cooling: indoor temp. of 67°F (37°C) WB. 85°F(29.4°C) inlet water and 25.4 gpm water volume. Heating: indoor temp. of 70°F (21.1°C) DB. 70°F(21.1°C) inlet water and 25.4 gpm water volume. Equivalent piping length: 25ft (7.5 m) RWEYQ-P Water Cooled Inverter Series...
EDUS30-900-R Field Wiring 7. Field Wiring RWEYQ72, 84, 144, 168, 216, 252PTJU [Operation System : Heat Recovery] RWEYQ-P Water Cooled Inverter Series...
Page 15
Field Wiring EDUS30-900-R RWEYQ72, 84, 144, 168, 216, 252PTJU [Operation System : Heat Pump] *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
22.4+22.4 +22.4 : Max. Overcurrent Protection (A) MOP is used to select the circuit breaker and the ground fault circuit interrupter (ground leakage circuit breaker). 3D066048 *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
Page 18
Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F RWEYQ-P Water Cooled Inverter Series...
Page 19
Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
Page 20
Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
Page 21
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 22
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 23
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 24
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 25
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 26
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 27
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 28
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 29
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 30
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 31
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 32
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 33
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 34
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 36
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 37
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 38
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 39
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 40
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 41
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 42
Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 43
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 44
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 45
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 46
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 47
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 48
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 49
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 50
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 51
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
Page 52
Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
15.9 gal/min (60.2 l/min) 3. When cooling load is small, the indoor unit may initiate thermostat-off for freeze protection; this is only for a limited amount of time. 4. Hold ambient conditions at 35~95°F, (1.6~35°C)~80%RH. RWEYQ-P Water Cooled Inverter Series...
Page 57
15.9 gal/min (60.2 l/min) 3. When the cooling load is small, the indoor unit may initiate thermostat-off for freeze protection; this is only for a limited period of time. 4. Hold ambient conditions at 35~95°F, (1.6~35°C)~80%RH. 3D066043 RWEYQ-P Water Cooled Inverter Series...
It is highly recommended to consult your local Daikin representative for design assistance. 5. In heating operation a minimum of 30% ethylene glycol is required when operating at an EWT of 50~23°F (10~ 5°C) and 40% when operating between 23~14°F (5 ~ 10°C).
Front due to environmental noise and sound reflection. ( V2469 ) Octave Band Level RWEYQ72PTJU RWEYQ84PTJU OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) 4D055414 4D055415 RWEYQ-P Water Cooled Inverter Series...
• Installation manual • Operation manual Shape Black Note: The accessory pipe for discharge gas is used for the heat recovery system. (Not used for the heat pump system.) Optional Accessories (For Unit) KRC19-26A6 3D066050 RWEYQ-P Water Cooled Inverter Series...