Daikin RWEYQ-P Engineering Data
Daikin RWEYQ-P Engineering Data

Daikin RWEYQ-P Engineering Data

Water cooled inverter series –heat pump / heat recovery-60hz

Advertisement

EDUS 30 - 900 - R
RWEYQ-P
AMERICAS
AMERICAS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RWEYQ-P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin RWEYQ-P

  • Page 1 EDUS 30 - 900 - R RWEYQ-P AMERICAS AMERICAS...
  • Page 2: Table Of Contents

    9.1 Cooling Capacity ..................16 9.2 Heating Capacity ..................34 9.3 Capacity Correction Factor................. 52 10. Standard Operation Limits ...............55 11. Geothermal Operation Limits ..............57 12. Sound Levels (Reference) ...............58 13. Accessories....................59 13.1 Strainer Kit - BWU26A20................60 RWEYQ-P Water Cooled Inverter Series...
  • Page 3: Specifications

    2. This unit cannot be installed outdoors. Install indoors (Machine room, etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RH Heat rejection from the casing : 0.64kW 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
  • Page 4 2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6 ~ 35°C), ~80%RH Heat rejection from the casing : 0.71kW 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
  • Page 5 2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RHHeat rejection from the casing : 0.64kW x 2 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
  • Page 6 2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RH Heat rejection from the casing : 0.71kW x 2 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
  • Page 7 2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F(1.6~35°C), ~80%RH Heat rejection from the casing : 0.64kW x 3 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
  • Page 8 2. This unit cannot be installed outdoors. Install indoors (Machine room etc). 3. Hold ambient condition at 35~95°F (1.6~35°C, ~80%RH Heat rejection from the casing : 0.71kW x 3 4. There are some cases where capacity decreases depending on operating states. RWEYQ-P Water Cooled Inverter Series...
  • Page 9: Performance

    Cooling: indoor temp. of 67°F (37°C) WB. 85°F(29.4°C) inlet water and 25.4 gpm water volume. Heating: indoor temp. of 70°F (21.1°C) DB. 70°F(21.1°C) inlet water and 25.4 gpm water volume. Equivalent piping length: 25ft (7.5 m) RWEYQ-P Water Cooled Inverter Series...
  • Page 10: Dimensions

    EDUS30-900-R Dimensions 3. Dimensions RWEYQ72PTJU / RWEYQ84PTJU RWEYQ-P Water Cooled Inverter Series...
  • Page 11: Service Space

    Service Space EDUS30-900-R 4. Service Space RWEYQ72PTJU / RWEYQ84PTJU RWEYQ-P Water Cooled Inverter Series...
  • Page 12: Piping Diagrams

    EDUS30-900-R Piping Diagrams 5. Piping Diagrams RWEYQ72PTJU / RWEYQ84PTJU 4D066041 RWEYQ-P Water Cooled Inverter Series...
  • Page 13: Wiring Diagrams

    Wiring Diagrams EDUS30-900-R 6. Wiring Diagrams RWEYQ72PTJU / RWEYQ84PTJU RWEYQ-P Water Cooled Inverter Series...
  • Page 14: Field Wiring

    EDUS30-900-R Field Wiring 7. Field Wiring RWEYQ72, 84, 144, 168, 216, 252PTJU [Operation System : Heat Recovery] RWEYQ-P Water Cooled Inverter Series...
  • Page 15 Field Wiring EDUS30-900-R RWEYQ72, 84, 144, 168, 216, 252PTJU [Operation System : Heat Pump] *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
  • Page 16: Electric Characteristics

    22.4+22.4 +22.4 : Max. Overcurrent Protection (A) MOP is used to select the circuit breaker and the ground fault circuit interrupter (ground leakage circuit breaker). 3D066048 *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
  • Page 17: Capacity Table (Reference Data)

    Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
  • Page 18 Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F RWEYQ-P Water Cooled Inverter Series...
  • Page 19 Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
  • Page 20 Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. *Contact your local Daikin representative for EWT below 50°F. RWEYQ-P Water Cooled Inverter Series...
  • Page 21 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 22 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 23 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 24 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 25 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 26 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 27 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 28 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 29 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 30 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 31 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 32 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 33 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 34 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 35: Heating Capacity

    Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 36 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 37 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 38 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 39 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 40 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 41 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 42 Water Flow Head loss Total capacity ; MBh Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 43 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 44 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 45 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 46 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 47 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 48 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 49 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 50 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 51 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 52 Total capacity ; MBh Water Flow Head loss Power Input ; kW (Comp.) Water volume 13.2 15.9 25.4 31.7 39.6 Head loss FT HD 13.2 17.6 *This value shows the amount of head loss per one unit. RWEYQ-P Water Cooled Inverter Series...
  • Page 53: Capacity Correction Factor

    Capacity Table (Reference Data) EDUS30-900-R Capacity Correction Factor RWEYQ72, 216, 252PTJU 3D066046 RWEYQ-P Water Cooled Inverter Series...
  • Page 54 EDUS30-900-R Capacity Table (Reference Data) RWEYQ84, 168PTJU 3D066052 RWEYQ-P Water Cooled Inverter Series...
  • Page 55 Capacity Table (Reference Data) EDUS30-900-R RWEYQ144PTJU 3D066111 RWEYQ-P Water Cooled Inverter Series...
  • Page 56: Standard Operation Limits

    15.9 gal/min (60.2 l/min) 3. When cooling load is small, the indoor unit may initiate thermostat-off for freeze protection; this is only for a limited amount of time. 4. Hold ambient conditions at 35~95°F, (1.6~35°C)~80%RH. RWEYQ-P Water Cooled Inverter Series...
  • Page 57 15.9 gal/min (60.2 l/min) 3. When the cooling load is small, the indoor unit may initiate thermostat-off for freeze protection; this is only for a limited period of time. 4. Hold ambient conditions at 35~95°F, (1.6~35°C)~80%RH. 3D066043 RWEYQ-P Water Cooled Inverter Series...
  • Page 58: Geothermal Operation Limits

    It is highly recommended to consult your local Daikin representative for design assistance. 5. In heating operation a minimum of 30% ethylene glycol is required when operating at an EWT of 50~23°F (10~ 5°C) and 40% when operating between 23~14°F (5 ~ 10°C).
  • Page 59: Sound Levels (Reference)

    Front due to environmental noise and sound reflection. ( V2469 ) Octave Band Level RWEYQ72PTJU RWEYQ84PTJU OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) 4D055414 4D055415 RWEYQ-P Water Cooled Inverter Series...
  • Page 60: Accessories

    • Installation manual • Operation manual Shape Black Note: The accessory pipe for discharge gas is used for the heat recovery system. (Not used for the heat pump system.) Optional Accessories (For Unit) KRC19-26A6 3D066050 RWEYQ-P Water Cooled Inverter Series...
  • Page 61: Strainer Kit - Bwu26A20

    32 ~ 158˚F Design pressure BWU26A20 (284 PSI) Mesh size 50 mesh Flowing Quantity Characteristics: Water Flow Head Loss (FT HD) BWU26A20 14.5 (33.4) 1.45 (3.34) (2.3) 0.15 (0.4) 13.2 25.4 26.4 39.6 264.2 (gal/min) Flowing Rate RWEYQ-P Water Cooled Inverter Series...
  • Page 62 AMERICAS 1645 Wallace Drive, Suite 110 Carrollton, TX75006 info@daikinac.com www.daikinac.com Specifications, designs and other content appearing in this brochure are current as of March 2010 but subject to change without notice. EDUS30-900-R Printed in U.S.A. 03/10 AK·FS.K...